What Is a Dowel Bar in Concrete?

A dowel bar is a short bar that crosses a joint between two concrete pours. One part of it is cast into the first pour and the other part sticks out to be cast into the next one, so the two pieces of concrete are tied together or can pass load across the joint. On drawings it is often abbreviated DWL or DWLS.
Where you see dowel bars on a drawing
On the drawing you will see two different kinds of dowel:
Deformed rebar dowels connect elements that are poured at different times:
- Footing to column:
(4) #6 DWLS TO MATCH COL VERTS - Footing to wall:
#5 DWLS @ 12" TO MATCH WALL VERTS - Slab to wall, or new concrete to existing (drilled and epoxied dowels)
These are usually L-shaped: a hook or bend sits on the footing bottom mat, and the straight leg projects up to lap with the column or wall bars above.
Smooth dowels are used at joints in slabs on grade and pavements. They are plain round bars (often coated or greased on one side) placed at mid-depth across a contraction or construction joint. They transfer load across the joint but let the slab move along the dowel. They are not lapped with anything.
More on where pour breaks happen in construction joints and rebar.
What dowel bars change in a takeoff
Dowels are a separate line item. They usually appear only in sections and details, not on the plan, so they are easy to miss. For footing dowels, the count normally matches the vertical bars of the column or wall they connect to, and the length is the embedment into the footing plus the lap or projection above it.
Worked example
A building has 12 spread footings, each with a column of (4) #6 VERTS. The footing detail shows (4) #6 DWLS with a 12 in leg on the footing mat, 18 in vertical inside the footing, and a 36 in projection above the footing. (Take the real values from the project's detail and notes.)
| Step | Value |
|---|---|
| Dowel length | 12 + 18 + 36 = 66 in = 5.5 ft |
| Dowels per footing | 4 |
| Footings | 12 |
| Total dowels | 4 x 12 = 48 |
| Total length | 48 x 5.5 = 264 ft |
| Weight (#6 at 1.502 lb/ft) | about 397 lb |
For wall dowels, count them like any spaced bar: wall length divided by spacing, plus one. See how to estimate rebar for footings.
A common mistake
The most common mistake is not taking off the dowels at all, because the plan shows the footing bars and the column schedule shows the column bars, and the dowels live only in a detail between the two. The second mistake is counting the column verticals all the way down into the footing and then counting the dowels as well, which doubles that steel. Read the column reinforcement detail to see whether the verticals stop at the top of the footing and the dowels take over.
Frequently asked questions
Why are dowels needed between a footing and a column?
The footing is usually poured before the column. Dowels cast into the footing stick up so the column bars can lap with them, which carries the column forces into the footing across the pour joint.
What is the difference between a dowel and a starter bar?
Starter bar is the common British and Australian term for the same thing: bars cast into one pour that project to lap with the bars of the next.
Are slab dowels the same as rebar dowels?
No. Slab and pavement dowels at joints are usually smooth bars that let the slab move along the joint, while rebar dowels are deformed bars that tie the two pours together.
This article explains general practice for learning purposes. On a real project, the drawings, the general notes and the governing code always win.